Bakar, Ab Halim Abu and Talib, D.N.A. and Mokhlis, Hazlie and Illias, Hazlee Azil (2013) Lightning back flashover double circuit tripping pattern of 132 kV lines in Malaysia. International Journal of Electrical Power & Energy Systems, 45 (1). pp. 235-241. ISSN 0142-0615, DOI https://doi.org/10.1016/j.ijepes.2012.08.048.
Full text not available from this repository.Abstract
This paper presents a study on flashover patterns due to double tripping using EMTP software. The simulation was performed on a 132 kV line double circuit for economic installation of transmission line arresters (TIAs). The simulation results were validated with the field data of 132 kV transmission line in Malaysia. A vertically configured double circuit transmission line was modelled and the effects of tower footing resistance, lighting current values, power frequency voltage and the coupling effect of the phase conductors study were taken into account. A good agreement between the simulation and field data was obtained. A specific back flashover phase of the double circuit line can be determined by considering the effects that have been mentioned. Through determination of the tripping pattern, a suitable installation of line arresters and mitigation of line tripping due to back flashover can be achieved.
Item Type: | Article |
---|---|
Funders: | UNSPECIFIED |
Additional Information: | Times Cited: 0 Bakar, A. H. A. Talib, D. N. A. Mokhlis, H. Illias, H. A. |
Uncontrolled Keywords: | Emtp, double circuit tripping, back flashover, power frequency voltage, coupling effects, footing resistance. |
Subjects: | T Technology > TA Engineering (General). Civil engineering (General) T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Faculty of Engineering |
Depositing User: | Mr Jenal S |
Date Deposited: | 15 Jul 2013 00:32 |
Last Modified: | 06 Dec 2019 08:37 |
URI: | http://eprints.um.edu.my/id/eprint/7797 |
Actions (login required)
View Item |